Delta-wye transformer

From Wikipedia, the free encyclopedia
Jump to navigation Jump to search

Template:Short description Script error: No such module "Distinguish".

File:Diapositiva14.PNG
An example delta-wye transformer schematic.

A delta-wye transformer is a type of three-phase electric power transformer design that employs delta-connected windings on its primary and wye/star connected windings on its secondary. A neutral wire can be provided on wye output side. It can be a single three-phase transformer, or built from three independent single-phase units. An equivalent term is delta-star transformer.

Transformers

File:DeltaWyeTransformer.svg
One possible delta-wye transformer configuration.[1]

Delta-wye transformers are common in commercial, industrial, and high-density residential locations, to supply three-phase distribution systems.

An example would be a distribution transformer with a delta primary, running on three 11 kV phases with no neutral or earth required, and a star (or wye) secondary providing a 3-phase supply at 415 V, with the domestic voltage of 240 available between each phase and the earthed (grounded) neutral point.

The delta winding allows third-harmonic currents to circulate within the transformer, and prevents third-harmonic currents from flowing in the supply line.[2]

Delta-wye transformers introduce a 30, 150, 210, or 330 degree phase shift.[3] Thus they cannot be paralleled with wye-wye (or delta-delta) transformers. However, they can be paralleled with identical configurations and some different configurations of other delta-wye (or wye-delta with some attention) transformers.Script error: No such module "Unsubst".

See also

References

Template:Reflist

External links

Template:Electric transformers

  1. Script error: No such module "citation/CS1".Template:Dead link
  2. Electrical Transmission and Distribution Reference Book, Westinghouse Electric Corporation, 1964, Chapter 5, table 15.
  3. Script error: No such module "citation/CS1".Template:Dead link